• One For allIndustrial Automation , Instrumentation & Valve

Z109UI2

Z109UI2 is a device that accepts mA/V signals able to convert it into mA/V standard signals. It’s configurable either for monopolar or bipolar inputs and all parameters are configurable through dipswitches. The device can power also all 2-wire sensors. A 3-way galvanic isolation among Power supply // input // output circuits assures the integrity of your datas.

Technical Specification



General Data
Power supply 10..40 Vdc / 19..28 Vac / 50-60 Hz
Power consumption 2,5 W
Isolation 1.500 Vac (3 way)
Power transducers Yes
Accuracy 0,1%
Response time 35 ms (11 bit)..140 ms (16 bit)
Status Indicators Power supply, error, data transmission, data reception, input status
Dimension (W x H x D) 17.5 x 100 x 112 mm
Setting Dip- switches
EASY_Z109 (PC software)
Test-3 (hand held calibrator)
Protection Degree IP20
Mounting 35 mm DIN rail guide
Operating Temperature -10..+60 °C


Input
Channel Numbers 1
Voltage ((mV, V)
Bipolar from 75 mV to 20 V
 Resolution 15 bit + sign
Current 2 Bipolar up to 20 mA (active/passive)
Resolution 1 μA


Output
Channel Numbers 1
Voltage 4 scales: 0..1, 0..5, 0..10, 2..10 V
Min load resistance: 2.000 Ω
Current 2 scales: 0/4..20 mA (active/passive)
Max load resistance: 600 Ω


Standard
Norms EN 50081-2; EN 55011; EN 50082-2; EN 61000-2-2/4; EN 50140/141; EN 61010-1
Approval CE, UL-CSA


order codes
Code Description
Z109UI2 DC current/voltage isolator/converter,
Power supply 10..40 Vdc / 19..28 Vac