• One For allIndustrial Automation , Instrumentation & Valve

T201DC-100

T01DC100 is an isolated and passive, contact-less loop powered direct current transducer. The T201DC100 has functions and look very similar to a standard current transformer, but it has stress features of measuring the continuous current component that pass-through it. For its electrical endurance, ease of use and compact dimensions, the T201DC100 fits every kind of current measurement to 100 Adc.

Technical Specification



GENERAL FEATURES
Accuracy class | 0.2 |
Max error 0.1% + 14 μA (measure)
0.05% + 4 μA (output)
Coeff. temperatura < 150 ppm/K
EMI error < 50 μA
Response time 100 ms (without filter)
 600 ms (with filter)
Protection degree IP 20
Operating temperature -10..+65°C
Humidity 10..90% non condensing
Weight 47 g
Dimensions 38 x 40 x 20 mm
Enclosure PBT, black
Configuration DIP-switches (range, filter)
Mouting DIN rail guide
Norms CE, EN 61000-6-4,
 EN 64000-6-2, EN 61010-1,
 EN 60742




INPUT
Connetion Passing- through hole
Hole diameter 12,5mm, 1/2 “)
Range Monopolar: 0..5 / 0..10 / 0..20 / 0..40 A
Bipolar: -5..+5 / -10..+10 / -5..+20 / -10..+40 A
Maximun rating > 1.000 A ± 300 A (correct reading range)
AC overlying (f > 35 Hz) -15..+50 A (allowable peak value)
 -10..+32 A (Full-wawe rectified)
-5..+16 A (Half-wawe rectified)
Isolation When a sheathed wire is used, the insulation voltage
is set by sheath properties. It’s stated 1 KVdc




OUTPUT / POWER SUPPLY
Type Passive current loop 4..20 mA.
Terminals Screw terminal pitch 5.08mm for max 2.5mm2 cables
Min Voltage 6 V
Max Voltage 30 V (directly wired)
100 V (with added resistor)
120 V (pulsed, directly wired))
Other protections Polarity reversal.
Loop current limiting on hardware fault.
Over-temperature
Max power dissipation 650 mW continuous.
 2.5 W pulsed (10 s).
1500 W.ms on surge (500 V, 40 )